5 Mounting
SMA Solar Technology America LLC
Installation ManualSTP50-US-40-IA-en_es-1118
5 Mounting
5.1 Requirements for Mounting
Requirements for the Mounting Location:
WARNING
Danger to life due to fire or explosion
Despite careful construction, electrical devices can cause fires.
Do not mount the product in areas containing highly flammable materials or gases.
Do not mount the product in potentially explosive atmospheres.
The mounting location must be suitable for the weight and dimensions of the inverter (see
Section10 "Technical Data", page56).
The mounting location should be freely and safely accessible at all times without the need for
any auxiliary equipment (such as scaffolding or lifting platforms). Non-fulfillment of these
criteria may restrict servicing.
The inverter can be mounted in a position that is directly exposed to solar irradiation. There is,
however, the possibility that the inverter reduces its power output to avoid overheating due to
high temperatures.
The DC load-break switch of the inverter must always be freely accessible.
Climatic conditions must be met (see Section10 "Technical Data", page56).
ENGLISH