EasyManua.ls Logo

SMA SUNNY TRIPOWER CORE1-US - Updating Inverter Firmware

SMA SUNNY TRIPOWER CORE1-US
126 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
10 Technical Data
SMA Solar Technology America LLC
Installation Manual STP50-US-40-IA-en_es-11 57
Limits of accuracy of time measurement at nomi-
nal trip time
± 0.1%
Limits of accuracy of current measurement 1% of the AC current
Limits of accuracy of power (active/reactive)
measurement
5% of the nominal AC power
Limits of accuracy of power factor measurement 0.01
Limits of accuracy of time measurement 0.001s
Output power at +60°C (+140°F) at 500V
MPP
>34kVA
Output power at +60°C (+140°F) at 800V
MPP
>38.5kVA
Power factor at rated power 1
Range of the displacement power factor (ad-
justable)
0.0overexcitedto0.0underexcited
Feed-in phases 3
Phase connection 3 (+1)
Overvoltage category in accordance with
UL1741
IV
* Depending on the configured country data set
Efficiency
Maximum efficiency, η
max
98.2%
CEC efficiency, η
CEC
98.0%
Multifunction relay
Maximum DC switching voltage 30V
Maximum AC switching current 1.0A
Maximum DC switching current 1.0A
Minimum load 0.1W
Minimum electrical endurance when the maxi-
mum switching voltage and maximum switching
current are complied with*
100000 switching cycles
* Corresponds to 20years at 12switching operations per day
Protective Devices
DC reverse polarity protection Short-circuit diode
Input-side disconnection point DC load-break switch
Output-side service switch, listed in accordance
with UL508
AC load-break switch
ENGLISH

Table of Contents

Other manuals for SMA SUNNY TRIPOWER CORE1-US

Related product manuals