Table 6 – Terminal Connection Description 
Connected to negative of starter battery. 
Connected to positive of starter battery. If wire length is 
over  30m,  better  to  double  wires  in  parallel.  Max.  20A 
fuse is recommended. 
Connected to B+ via emergency stop button. 
B+ is supplied by 3 points, rated 16A. 
B+ is supplied by 3 points, rated 16A Connect to starter 
coil. 
B+ is supplied by 2 points, rated 7A. 
Normal close output, 7A rated. 
Normal open output, 7A rated. 
Relay  normal  open  volt-free  contact 
output. 
16A rated. 
Connect to D+ (WL) terminal. If without, the terminal is 
hung up.   
Connected  to  speed  sensor,  shielding  line  is 
recommended. 
Speed  Sensor  Input  (B- 
connected inside) 
Connect  to  water/cylinder  temp. 
resistance type sensor. 
Oil Pressure Sensor Input 
Connect  to  oil  pressure  resistance 
type sensor. 
Connect to fuel level resistance type 
sensor. 
Ground connected is active (B-). 
Ground connected is active (B-). 
Ground connected is active (B-). 
Connect secondary coil (rated 5A). 
Connect secondary coil (rated 5A). 
Connect secondary coil (rated 5A). 
Refer to INSTALLATION description. 
Gens  U  phase  Voltage 
Sensing Input 
Connect to U phase output (2A fuse is recommended). 
Gens  V  phase  Voltage 
sensing Input 
Connect to V phase output (2A fuse is recommended). 
Gens  W  phase  Voltage 
Sensing Input 
Connect to W phase output (2A fuse is recommended). 
Connect to generator N-wire.