HGM6110/6120 AUTO START MODULE
HGM6110/6120 Auto Start Module ISSUE 2.0 2008-10-27 Page 11 of 24
LOW OIL PRESSURE, if the module detects that the engine oil pressure has
fallen below the low oil pressure setting level after the Safety On timer has
expired, a shutdown will occur.
OVERSPEED, if the engine speed exceeds the setting value a shutdown is
initiated.
UNDERSPEED, if the engine speed falls below the setting value after the Safety
On timer has expired, a shutdown is initiated.
LOSS OF SPEED SIGNAL, if the speed sensing signal is lost, a shutdown is
initiated.
GENERATOR OVER FREQUENCY if the module detects a generator output
frequency in excess of the setting value a shutdown is initiated.
GENERATOR UNDER FREQUENCY, if the module detects a generator output
frequency below the setting value after the Safety On timer has expired, a
shutdown is initiated.
GENERATOR OVER VOLTAGE if the module detects a generator output voltage
in excess of the setting value a shutdown is initiated.
GENERATOR UNDER VOLTAGE if the module detects a generator output
voltage below the setting value after the Safety On timer has expired, a shutdown
is initiated.
GENERATOR OVER CURRENT, if the module detects a generator output current
in excess of the setting value is initiated, a shutdown is initiated.
FAIL TO START, if
the
engine does not fire after the pre-set number of attempts
has been made a shutdown will be initiated.
AUXILIARY INPUTS, if an auxiliary
input
has been configured as a shutdown the
appropriate information will be displayed.