3. SPECIFICATION
Operating Voltage DC8. 0V to 35. 0V, Continuous Power Supply
Power Consumption <3W
Alternator Input Range
3-Phase 4 Wire
2-Phase 3 Wire
Single phase 2 wire
15V AC - 360 V AC (ph-N)
15V AC - 360 V AC (ph-N)
15V AC - 360 V AC (ph-N)
Alternator Input Frequency 50Hz - 60 Hz at rated engine speed
Magnetic Input Range +/- 0. 5 V to 70 V Peak
Magnetic Input Frequency 10,000 Hz (max) at rated engine speed.
Start Relay Output 7 Amp DC at supply voltage.
Fuel Relay Output 7 Amp DC at supply voltage.
Auxiliary Relay Output (1-4)
17 Amp DC at supply voltage2
7A 250VAC free
voltage contact3,416A 250VAC free voltage contact.
Dimensions 200mm x 144mm x 50mm
Panel cutout 184mm x 139mm
Operating Temperature Range -25 to +70°C
Storage Condition Temperature: (-30 - 80)°C
C. T. Burden 2. 5VA
C. T. Secondary 5A
Weight 0. 55kg
4. OPERATION
4.1 KEY FUNCTION
Stop/ Reset key
This button places the module into its Stop/reset mode.
When engine is running, pressing this key will stop the
engine. When a shutdown alarm occur, pressing this key will
reset alarm. In stop mode, pressing this key over 3 second
will test LED mounted on the panel.
Start key
In manual or manual test mode, pressing this key will start
engine.
Manual mode key Pressing this key will set the module into manual mode.
Auto key Pressing this key will set the module into automatic mode.