•Analogue I/O unit parameters (2)
Parameter
setting
No. Parameter Definition Item Content
Default
setting
By
E.O.
By
W.S.
Enable Generates an error.
1
User’s set
value lower
limit error
Generates error
per channel when
the input or output
value falls below
the lower limit.
Disable
Does not generate an
error.
Enable
Generates an error.
Val: -32767 to 32766
8
Scale lower
limit setting
Sets the scale
lower limit.
Generates error
per channel when
the input or output
value falls below
the lower limit.
Disable
Does not generate an
error.
Val: -32767 to 32766
Val: 0
Enable
Output will be user fault
value.
1
9
Output setting
for
communication
fault
2
Set output per
channel when
communication is
abnormal.
Disable
Output will be held last
state.
Enable
Output will be user idle
value.
1
10
Output setting
for
communication
idling
2
3
Sets output per
channel during
communication
idling.
Disable
Output will be held last
state.
1: Set value shall be set per analogue output range within settable range in the table below.
When the analogue output range is changed, check the set value and change it to an appropriate value.
2: This function is valid only when “Hold/Clear priority” of the system parameter is set to “Via software“.
3: Some PLC does not support an idle mode.

Other manuals for SMC Networks EX600 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SMC Networks EX600 Series and is the answer not in the manual?

SMC Networks EX600 Series Specifications

General IconGeneral
BrandSMC Networks
ModelEX600 Series
CategoryI/O Systems
LanguageEnglish

Related product manuals