In ITV for IO-Link, you can set "lock / unlock" for data storage function.
Locking data storage function will invalidate data storage function.
When backing up data storage (Parameter setting data read) or restoring
(Overwriting parameter setting data) is instructed while data storage
function is locked, the access rejection is answered.
Default: 0(unlock)
Unlocking the data storage function
(Available data storage function)
Data storage function lock.
(Disable data storage function.)
* indicates the initial shipping value.
The response time can be changed by tuning the gain. When the gain is
increased, the response time tends to be faster, but stability will be lost,
which may cause hunting (unstable pressure).
Default: Gain 9
* indicates the initial shipping value.