○Error indication
This function is to display error location and content when a problem or an error occurs.
The switch output load current is
more than 80 mA.
Turn the power off and remove the cause
of the over current.
Then turn the power on.
During zero clear operation, pressure
above ±3.5%F.S. has been applied.
After 1 second, the mode will return
to measurement mode. The zero
clear range can vary ±1%F.S. with
individual product differences.
Perform zero clear operation again after
restoring the applied pressure to an
atmospheric pressure condition.
Pressure has exceeded the upper
limit of the set pressure range.
Adjust the applied pressure to a level
within the set pressure range.
Pressure has exceeded the lower
limit of the set pressure range.
Displayed in the case of an internal
data error.
Turn the power off and turn it on again.
If resetting fails, an investigation by SMC
Corporation will be required.
If the error can not be reset after the above measures are taken, then please contact SMC.