COMPLIANCE
European EMC Directive No. 2004/108/EC (15/12/2004)
LV Directive No. 2006/95/EC Dated 12 December 2006
IEC 62053-21 / IEC 62052-11
SYSTEM CONNECTION
Supply types / number of wires Single phase 2 wires 230V
Three phase 3 wires 3x230V / 3x400V and Three phase 4 wires
3x230/400V
Management Detection of cabling error
Frequency 50 and 60 Hz (± 5 Hz)
SUPPLY Autosupplied
CONSUMPTION
Supply < 10 VA or 2 W
Current circuit < 2.5 VA
CURRENT (TRMS)
Starting current (Ist) 80 mA
Minimum current (Imin) 0.5 A
Transition current (Itr) 2 A
Reference current (Iref) 20 A
Permanent overload (Imax) 100 A
Short-term over-current 3000 A for 10 ms (EN50470-3 and IEC 62053-21)
VOLTAGE (TRMS)
Direct measurement 230VAC Phase/Neutral 400V AC Phase/Phase ± 15%
Permanent overload 230 / 400 V AC + 15%
POWERS
Active Yes
Reactive No*
Resolution 0.1 kW
ENERGY
Active Yes
Reactive No*
Total and partial metering Yes (0 to 999999.9 kWh)
Bidirectional metering (EA+ and EA-) Yes
Resolution 1 kWh
Interval ---
Load curve ---
Integration time for load curves ---
ACCURACY
Active energy Class 1 (IEC 62053-21)
TARIFFS
Tariff management No*
Number of tariffs managed 4*
Tariff exchange input No*
METROLOGICAL LED
Impulse weight 500 impulses / kWh or 2Wh / impulse
Colour Red
DISPLAY
Type 7 Digit LED with blue back-lighting
Refresh time 1s
Back-lighting illumination time 30 s
List of functions displayed Cf. table below.
* Functions available only via communication, the complete list of these functions is given in the down-
loadable JBUS/MODUS communication table.
41
COUNTIS E33
GB