10
EN
COUNTIS E47/E48 - 547224A - SOCOMEC
6. CONNECTION
6.1. Connecting the COUNTIS E47/E48
SET
N
1 2
L1
A V A A V A A V A
L2 L3
Fixed / exible
0.14 mm
2
->
2.5mm
2
0.27" / 6.9 mm
PZ2
4.5 lb.in /
0.5 Nm max.
Fixed / exible
1.5 mm
2
->
35mm
2
0.47" / 12 mm
PZ2
17.70 lb.in /
2 Nm max.
6.2. Connection to the electrical network and to the loads
The COUNTIS E47/E48 are intended for three-phase networks with neutral.
3 phases, 4 wires, 3CT
Ethernet
RJ45. The Ethernet cable must pass twice through
the ferrite core, positioned at least 5cm away from the
device.
Pulse output
1: -
2: +
Optocoupler pulse outputs
Terminals 1-2 must be supplied with voltage between
5 and 27 VDC (27mA max)
Mains
L1 A: Current input/output
L1 V: Voltage input
L2 A: Current input/output
L2 V: Voltage input
L3 A: Current input/output
L3 V: Voltage input
N: Neutral connection
SET
N
L1
L2
L3
N
3 x 0.5A
230/400 VAC 50/60 Hz
Ethernet*
1 2
L1
A V A A V A A V A
L2 L3
- +