EasyManuals Logo

socomec DELPHYS MX Technical Guide

socomec DELPHYS MX
10 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #8 background imageLoading...
Page #8 background image
88
STANDARD AND OPTIONS
Electrical characteristics - Inverter
Rated power (kVA) 250 300 400 500 800 900
Rated output voltage (selectable) 380/400/415 V
Outputvoltagetolerance
Static: < 1%
Dynamic: (0-100% Pn) ±2%
Rated output frequency 50/60 Hz (selectable)
Outputfrequencytolerance 0.02 on mains power failure
Load crest factor (according IEC 62040-3) 3:1
Voltage harmonic distortion (ThdU)
< 2% on linear load
<4%ondistortingload(Ph/N)
< 2% on linear load
< 2.5% on distorting load
(Ph/N)
Overloadtoleratedbytheinverter
(with mains power present)
125% x 10 min
150% x 1 min
Electrical characteristics - Efficiency
Rated power (kVA) 250 300 400 500 800 900
Double conversion efficiency
(normal mode)
93.5% at full load
Efficiency in Eco Mode 98%
Electrical characteristics - Environment
Rated power (kVA) 250 300 400 500 800 900
Storage temperatures
-20to+70°C(-4to158°F)
(15to25°Cforbetterbatterylife)
Working temperature
0to+35°C(32to95°F)
(15to25°Cforbetterbatterylife)
0to+35°C(32to95°F)
(1)
(15to25°Cforbetter
battery life)
Maximum relative humidity
(non-condensing)
95%
Maximum altitude without derating 1000 m (3300 ft)
Degree of protection IP20 (up to IP52 optional)
Portability EN60068-2
Colour RAL9006(GreyToyo)
(1) Conditions apply.

Other manuals for socomec DELPHYS MX

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the socomec DELPHYS MX and is the answer not in the manual?

socomec DELPHYS MX Specifications

General IconGeneral
Brandsocomec
ModelDELPHYS MX
CategoryUPS
LanguageEnglish