EasyManua.ls Logo

socomec DELPHYS MX - Page 8

socomec DELPHYS MX
10 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
88
STANDARD AND OPTIONS
Electrical characteristics - Inverter
Rated power (kVA) 250 300 400 500 800 900
Rated output voltage (selectable) 380/400/415 V
Outputvoltagetolerance
Static: < 1%
Dynamic: (0-100% Pn) ±2%
Rated output frequency 50/60 Hz (selectable)
Outputfrequencytolerance 0.02 on mains power failure
Load crest factor (according IEC 62040-3) 3:1
Voltage harmonic distortion (ThdU)
< 2% on linear load
<4%ondistortingload(Ph/N)
< 2% on linear load
< 2.5% on distorting load
(Ph/N)
Overloadtoleratedbytheinverter
(with mains power present)
125% x 10 min
150% x 1 min
Electrical characteristics - Efficiency
Rated power (kVA) 250 300 400 500 800 900
Double conversion efficiency
(normal mode)
93.5% at full load
Efficiency in Eco Mode 98%
Electrical characteristics - Environment
Rated power (kVA) 250 300 400 500 800 900
Storage temperatures
-20to+70°C(-4to158°F)
(15to25°Cforbetterbatterylife)
Working temperature
0to+35°C(32to95°F)
(15to25°Cforbetterbatterylife)
0to+35°C(32to95°F)
(1)
(15to25°Cforbetter
battery life)
Maximum relative humidity
(non-condensing)
95%
Maximum altitude without derating 1000 m (3300 ft)
Degree of protection IP20 (up to IP52 optional)
Portability EN60068-2
Colour RAL9006(GreyToyo)
(1) Conditions apply.