61
DIRIS A40/A41 - Ref.: 535 747 A
DIRIS A40 / A41
CARATTERISTICHE TECNICHE
MARCATURA CE
The DIRIS A40/A41 complies with :
The requirements of the European directive on electromagnetic compatibility (EMC) no. 89/336/CEE dated 3 May 1989,
modified by directive no. 92/31/CEE dated 28 April 1992 and by directive no. 93/68/CEE dated 22 July 1993.
Low voltage directive no. 73/23/CEE dated 19 February 1973, modified by directive no. 93/68/CEE dated 22 July 1993
modified by directive no. 2006/95/CE.
COMPATIBILITÀ ELETTROMAGNETICA
Immunity to electrostatic discharges: IEC 61000-4-2 - Level III
Immunity to radiated radio-frequency fields: IEC 61000-4-3 - Level III
Immunity to electrical fast transients/bursts: IEC 61000-4-4 - Level IV
Immunity to impulse waves: IEC 61000-4-5 - Level IV
Immunity to conducted disturbances: IEC 61000-4-6 - Level III
Immunity to power frequency magnetic fields: IEC 61000-4-8 - Level IV
Conducted and radiated emissions: IEC 61000-6-4 - Class B
Immunity to voltage dips and short interruptions: IEC 61000-4-11
CLIMA
Operating-temperature range: IEC 60068-2-1/IEC 60068-2-2
-10 °C to +55 °C
Storage temperature range: IEC 60068-2-1/IEC 60068-2-2
-20 °C to +85 °C
Humidity: IEC 60068-2-30 - 95 %
Saling fog: IEC 60068-2-52 - 2,5 % NaCl
CARATTERISTICHE MECCANICHE
Vibration from 10 to 50 Hz : IEC 60068-2-6 - 2 g
ISOLAMENTO
Installation category: III (480VAC ph/ph)
Degree of pollution: 2
Rated impulse withstand voltage: IEC 60947-1 - V imp: 4 kV
Front face: Classe II
Electric security: IEC 61010-1
I
CARATTERISTICHE DELLE «FUNZIONI DI VALUTAZIONE DELLA QUALITÀ DELL’ALIMENTAZIONE»
Simbolo delle funzioni Intervallo di misura Classe di prestazione di funzi-
onamento, secondo la norma CEI
61557-12
Altre caratteristiche
complementari
KI 1000 100 10 1
f 45 a 65 Hz 0,02 - - - -
I 0,1 a 1,2 A per TC 1A
0,5 a 6 A per TC 5A
0,2
--- -
In, Inc 0,1 a 1,2 A
per TC 1A
0,5 a 6 A per TC 5A
0,5 - - - -
U 50 a 600 V fase/fase 0,2 - - - -
Pst, Plt - - - -
Udip 50 a 600 V fase/fase 0,2 o
0,5
--- -
Uswl 50 a 600 V fase/fase 0,2 o
0,5
--- -
Uint 50 a 600 V fase/fase 0,5 - - - -
Unba - - - - -
Unb - - - - -
Uh 50 a 600 V fase/fase 1 - - - -
Ih 0,1 a 1,2 A per TC 1A
0,5 a 6 A per TC 5A
1--- -
Msv
- ---- -
Shop for Power Metering products online at:
1.888.610.7664
www.PowerMeterStore.com