DIRIS A40/A41 - RS485 - JBUS/MODBUS
®
54
DIRIS A40/A41 - Ref.: 536 103 B GB
COMMUNICATION
LIST OF PARAMETERS TO BE DISPLAYED OR PROGRAMMED (FUNCTION 3, 6 OR 16)
Decimal Hexa. Number Text Unit
address address of words
19 : ΣP predicted
20 : ΣQ predicted
21 : ΣS predicted
22 : T°C 1
23 : T°C 2
24 : T°C 3
25 : T°C internal
552 228 1 Lower threshold OUT 1
553 229 1 Unit lower threshold OUT 1:
0 : /
1 : k
2 : M
554 22A 1 Threshold value OUT 1
555 22B 1 Unit threshold value OUT :
0 : /
1 : k
2 : M
556 22C 1 Hysteresis 0 to 99 OUT 1 %
557 22D 1 SpeciedtimeOUT1 s.
558 22E 1 Relay status OUT 1:
0 : Open
1 : Closed
559 22F 1 Allocation of OUT 2 relay :
0 : Cde
1 : I
2 : U
3 : ΣP+
4 : ΣQ+
5 : ΣS
6 : F
7 : ΣPFL
8 : thd 3I
9 : thd 3U
10 : IN
11 : HOUR
12 : V
13 : thd In
14 : thd 3V
15 : ΣP-
16 : ΣQ-
17 : ΣPFC
18 : Cd-t
19 : ΣP predicted
20 : ΣQ predicted
21 : ΣS predicted
22 : T°C 1
23 : T°C 2
24 : T°C 3
25 : T°C internal
560 230 1 Lower threshold OUT 2
561 231 1 Unit lower threshold OUT 2:
0 : /
1 : k
2 : M