DIRIS A40/A41 - RS485 - JBUS/MODBUS
®
58
DIRIS A40/A41 - Ref.: 536 103 B GB
COMMUNICATION
LIST OF PARAMETERS TO BE DISPLAYED OR PROGRAMMED (FUNCTION 3, 6 OR 16)
Decimal Hexa. Number Text Unit
address address of words
17 : ΣPFC
18 : Cd-t
19 : T°C 1
20 : T°C 2
21 : T°C 3
22 : T°C internal
23 : ΣP predicted
24 : ΣQ predicted
25 : ΣS predicted
598 256 1 Lower threshold OUT 5
599 257 1 Unit lower threshold OUT 5 :
0 : /
1 : k
2 : M
600 258 1 Upper threshold OUT 5
601 259 1 Unit upper threshold OUT 5 :
0 : /
1 : k
2 : M
602 25A 1 Hysteresis 0 to 99 OUT 5 %
603 25B 1 SpeciedtimeOUT5 s.
604 25C 1 Relay status OUT 5 :
0 : Open
1 : Closed
605 25D 1 Allocation of OUT 6 relay:
0 : Cde
1 : I
2 : U
3 : ΣP+
4 : ΣQ+
5 : ΣS
6 : F
7 : ΣPFL
8 : thd 3I
9 : thd 3U
10 : IN
11 : HOUR
12 : V
13 : thd In
14 : thd 3V
15 : ΣP-
16 : ΣQ-
17 : ΣPFC
18 : Cd-t
19 : T°C 1
20 : T°C 2
21 : T°C 3
22 : T°C internal
23 : ΣP predicted
24 : ΣQ predicted
25 : ΣS predicted
606 25E 1 Lower threshold OUT 6
607 25F 1 Unit lower threshold OUT 6 :
0 : /