DIRIS Digiware D-50/D-70 displays can reduce the attack exposure by disabling certain peripherals or services that are
not essential to the customer’s use case.
Peripherals
- USB: disable the USB port of the D-50/D-70 display.
- Bluetooth Low Energy: disable the Bluetooth Low Energy of the D-50/D-70 display.
- Modbus slave over RS485: authorise or disable Modbus communication on the RS485 port of the D-50/D-70
display.
Email
- Make the secure version of SMTP mandatory for email notications in case of alarm on a connected device.
Field protocols
- Modbus Write function: authorise or disable to prevent people from changing settings over Modbus.
- SNMP: allow or disable the use of the SNMP protocol.
- BACnet: allow or disable the use of the BACnet protocol.
Data push
- Socomec cloud platform: authorise or block the export of data to the Socomec platform.
- Data export, FTPS mandatory: force the data export to an FTP server with a secure connection.