DIRIS Digiware M-50 & M-70 - 548751B - SOCOMEC
13. 10-STEP COMMISSIONING CHECKLIST FOR YOUR
DIGIWARE SYSTEM
1) Auto-discovery from M-50/M-70 push button or from EasyCong System software.
2) Conguration of DIRIS Digiware U and I modules via EasyCong System software.
3) Connection to the webserver (default IP address is 192.168.0.4).
4) Change default passwords for Admin, Advanced and Cyber security proles.
5) Connect to the Cyber security prole and generate the passphrase in case you lose your password.
6) Device discovery via “Devices” tab “Sources”.
7) Change load names and usages if necessary.
8) Optional: Hierarchy conguration (M-70 only).
9) Optional: Photoview conguration (M-70 only).
10) Conguration of IP conguration and communication protocols via “Protocols” menu.
Frequently Asked Questions
What happens if you lose your password ?
- If the Admin or Advanced Users lose their password, they can be changed from the Cyber security prole.
- If the Cyber security user loses his password, the passphrase can be used to create a new password.
- If the passphrase was lost, the only option is to reset the M-50/M-70 gateway to factory default settings.
How can I congure my IP conguration and communication protocols for my system ?
- Using EasyCong System.
- Or directly from the web server under the “Protocols” menu. Do not forget to reboot the M-50/M-70 gateway
after modifying the IP conguration.
Why is the ALARM LED on the M-50/M-70 ashing ?
- If this is the rst time you are using the DIRIS Digiware M-50/M-70 gateway, it could be that the default
passwords for the Advanced User, Admin and Cyber security proles have not been changed yet. The
“Password Alert” system alarm will be active until passwords are changed.
The Auto-discovery process is nished, yet some slave devices have not been detected.
If slave devices have not been detected, it could be because the Auto-discovery mode is set to “FAST”, which
only detects DIRIS Digiware modules, DIRIS B and DIRIS A-40 measuring devices. Use EasyCong System to
change the Auto-discovery mode to “FULL” to discovery all devices.