30~50mm
3~5mm
SOFAR 12000TL-G2
SOFAR 15000TL-G2
4-6 4-6
32A 32A
Cable and breaker selection
Model
For safety requirement, please use the quantified cable , or it may cause
cavle over heat even fire
The leakage current of breaker should be higher than 100mA and lower
than 300mA
Note
SOFAR 12000TL-G2
SOFAR 15000TL-G2
43 34
Cross area
( )
Maximum cable length (m)
6
4
25 20
10K~15KTL-G2 is three phase output inverter, it complies with related on-grid standard and
safety requirements.
AC cable installation steps
A. part cable length 30-50mm
B. part cable length 3-5mm
Isolation cover and terminals
can not be exposed
water-proff cover A
Crimp each core cable to OT terminal(KST, RNBL5-4 is recommended), after fixing , use
isolation tape to cover exposed part of OT(except O part).
Connect OT terminal to AC connector according to the painting then fix the water-proof cover.
SOFAR 10K~15KTL-G2
User manual
SOFAR 10K~15KTL-G2
User manual
SOFAR 10000TL-G2
4-6
32A
SOFAR 10000TL-G2
48
32
4.2