Insulating sleeve,
R type terminal terminal shall not be exposed.
Figure 4-8 AC cable connection instruction diagram (1)
Step 2: After assembling the PG waterproof connector, connect the cable to the AC
terminal block L1, L2, L3, N, PE contacts, and tighten the M8 screws (6-10 N.m) and
M6 screws (5-7 N.m) with a sleeve; Install AC shield screws(2~3 N.m);
Figure 4-9 AC cable connection instruction diagram (2)
Note: Copper/aluminum conversion terminal is required when aluminum wire is used, which is
delivered with the copper terminal.
4.4. Connect PV side of inverter(DC-Input)
Table 4.2 recommend DC input cable size (maximum tolerance voltage >= 1100V PV