If the alarm occurs occasionally, the
possible cause is that the electric grid is
abnormal occasionally. inverter automatically
returns to normal operating status when the
electric grid’s back to normal.
If the alarm occurs frequently, check
whether the grid voltage/frequency is within the
acceptable range. If no, contact technical
support. If yes, check the AC circuit breaker and
AC wiring of the inverter.
If the grid voltage/frequency is within the
acceptable range and AC wiring is correct, while
the alarm occurs repeatedly, contact technical
support to change the grid over-voltage,
under-voltage, overfrequency, under-frequency
protection points after obtaining approval from
the local electrical grid operator.
Check whether too few PV modules are
series connected in a PV string, thus the
voltage(Vmp) of the PV string is lower than the
minimum operating voltage of inverter. If yes,
adjust the number of series connected PV
modules to increase the voltage of the PV string
to fit the input voltage range of inverter. inverter
automatically returns to normal operating status
after correct adjustments.