Power factor
1 (+ / - 0.8 adjustable)
Inrush current
0.8A / 1us
Max output fault current
100A / 1us
System parameters
Max efficiency
Charge: 94.1% / discharge 94.3%
Standby losses
< 8W (PV SPS)
Topology
High frequency transformer isolated
Ingress protection ratings
IP 65
Safety protection
Anti-islanding, RCMU, ground fault monitoring
Communication
Wi-Fi, RS485, CAN2.0B
Environmental data
Ambient temperature range
-25C to +60C (derating above +45C)
Relative humidity range
0% - 100% (no condensing)
Protective class
Class I
Max operating altitude
2000m
Current transformer connection
Hard wired
General data
Noise
<25dB
Weight
20.5kg
Cooling
Natural convection
Dimensions (W*H*D)
532 x 360 x 173 mm
Display
LCD display
Warranty
5 years
EPS (Emergency Power Supply) data
EPS rated power
3000VA
EPS nominal voltage/frequency
230V, 50/60Hz
EPS rated current
13A
THDi
<3%
Switch time
20mS default