Leakage current
consistency error
Grid voltage
consistency error
SPI communication
error (DC)
SPI communication
error (AC)
Check the insulation resistance between the
photovoltaic array and ground (ground), if
there is a short circuit, the fault should be
repaired in time.
Check ac output PE wire for grounding.
Check the PV input mode
(parallel/independent mode) Settings for the
inverter. If not, change the PV input mode.
Check whether the CT wiring is correct.
Please check whether the fan 1 of inverter is
running normally.
Battery temperature
protection
Make sure the inverter is installed where
there is no direct sunlight.
Please ensure that the inverter is installed in
a cool/well ventilated place.
Ensure the inverter is installed vertically
and the ambient temperature is below the
inverter temperature limit.
Radiator 1 temperature
protection
Radiator 2 temperature
protection
Radiator 3 temperature
protection
Radiator 4 temperature
protection
Radiator 5 temperature
protection
Radiator 6 temperature
protection
Ambient temperature 1
protection
Ambient temperature 2
protection
Module 1 temperature
protection
Module 2 temperature
protection
Module 3 temperature
protection
Unbalanced bus voltage
RMS
Internal faults of inverter, switch OFF
inverter, wait for 5 minutes, then switch ON
inverter. Check whether the problem is
solved.
The transient value of
bus voltage is