ELECTRICAL CONNECTIONS
56 SOFAR 3 ... 6KTLM-G3
The inverter recognises all supported Demand Response commands
and initiates the reaction within two seconds.
Pin
Function
16
DRM1/5
15
DRM2/6
14
DRM3/7
13
DRM4/8
12
GND
11
DRM0
NOTE
Supported DRM commands: DRM0, DRM5, DRM6, DRM7,
DRM8.
Logic interface for VDE-AR-N 4105:2018-11
This function serves to control and/or limit the output power of the
inverter.
The inverter can be connected to a radio ripple control receiver in
order to dynamically limit the output power of all inverters within the
system.