EasyManua.ls Logo

SolarEdge SE9KUS - Technical Specifications - Three Phase Inverters (North America)

SolarEdge SE9KUS
101 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical Specifications - Three Phase Inverters (North America)
SE9KUS SE10KUS SE14.4KUS SE20KUS SE30KUS SE33.3KUS Units
Supported grid 120 / 208 277 / 480 120 / 208 277 / 480
OUTPUT
Rated AC power output 9000 10000 14400 20000 30000 33300 VA
Maximum AC power output 9000 10000 14400 20000 30000 33300 VA
AC Output Line Connections
3 Phase, 3-
wire / PE (L1-
L2-L3), TN, TT
3 phase, 4-
wire / PE (L1-
L2-L3-N), TN,
TT
3 phase, 4-
wire / PE (L1-
L2-L3-N), TN,
TT
3 Phase, 3-
wire / PE (L1-
L2-L3), TN, TT
3 phase, 4-
wire / PE (L1-
L2-L3-N), TN,
TT
3 phase, 4-wire / PE (L1-L2-L3-N), TN, TT
AC output voltage minimum-
nominal-maximum (L-N)
(1)
105-120-
132.5
244-277-305
105-120-
132.5
244-277-305 244-277-305 244-277-305 Vac
AC output voltage minimum-
nominal-maximum (L-L)
1
183-208-229
422.5-480-
529
183-208-229
422.5-480-
529
422.5-480-
529
422.5-480-
529
Vac
AC frequency min-nom-max
1
59.3 - 60 - 60.5
(with HI country setting 57 - 60 - 60.5)
Hz
Max. continuous output current
(per Phase)
25 12 40 24 36.5 40 A
Max. output fault current and
duration
73 / 150 51 / 150 92 / 150 73 /150 88 / 150 92 / 150 A / mS
Inrush current AC (Peak /
Duration)
2.6/20 4 /20 4.2 / 20 4.2 / 20
Aac(rms) /
ms
Max. back-feed current 0 A
Power factor range 1 (adjustable from -0.8 to +0.8)
GFDI threshold 1 A
Total harmonic distortion < 3 %
Utility monitoring, islanding
protection, country configurable
set points
Yes
INPUT
Maximum DC power 12150 13500 19400 27000 40500 45000 W
Transformer-less, ungrounded Yes
Maximum input voltage DC to
Gnd
250 490 300 490 490 490 Vdc
Maximum input voltage DC+ to
DC-
500 980 600 980 980 980 Vdc
Nominal input voltage DC to Gnd 200 420 200 420 420 420 Vdc
Nominal input voltage DC+ to DC- 400 840 400 840 840 840 Vdc
Maximum input current 26.5 13.5 38 26.5 39 40 Adc
Maximum short circuit current 45 Adc
Reverse-polarity protection Yes
Ground-fault isolation detection
1 M
Sensitivity
1 M
Sensitivity
350 k
Sensitivity
(2)
1 M
Sensitivity
350 k
Sensitivity
1
350 k
Sensitivity
1
Maximum inverter efficiency 97.1 98.2 97 98.1 98.5 98.5 %
CEC weighted efficiency 96.5 98 97 98 98.5 98.5 %
Night-time power consumption < 3 < 3 < 4 < 3 < 4 < 4 W
(1)
For other regional settings please contact SolarEdge Support.
(2)
Where permitted by local regulations
MAN-01-00527-1.2
Technical
Specifications
-
Three
Phase
Inverters
(North
America)
Technical Specifications - Three Phase Inverters (North America) 97

Table of Contents

Related product manuals