Battery
Charger
EPS System
(g-2)
(g-2-1)
(g-2-2)
g-2-1) Charger
Here the user can set the parameters of charger on this page, the inverter
is compatible with both lithium battery and lead-acid battery. Users can
set the charge & discharge parameters and awaken mode.
For the detailed parameters , please refer to below table.
>Min Capacity
10%
Charger
Charge Max
Charger
Current 25A
Setting Setting
Discharge Max
Charger
Current 25A
>Battery Awaken
Charger
NO
66
67
For Lithium battery
For Lead-acid-battery
Charge Absorp
Voltage
Charger
Charge Float
Voltage
0.0V
Charger
0.0V
Discharge cut
Voltage
0.0V
Charger
Charge Max
Current
Charger
0.0A
Discharge Max
Current
Charger
0.0A
When the battery voltage reachs the value( discharge cut voltage for lead-acid battery, min capacity for
lithium battery) in on-grid mode(no PV power), battery will stop discharging and the system will go into
ILDE mode.
When the battery voltage reachs this value( discharge cut voltage for lead-acid battery, min capacity for
lithium battery) in o-grid mode, battery will stop discharging and the inverter will stop exporting power
from EPS port with showing “BAT power low” on LCD display.
There are two ways to exit from BAT power low”.
-Press ESC button can exit from “BAT power low” manually.
-Enter EPS system setting page( refer to g-2-2 section) to exit from BAT power low” automatically.
NOTE !
PleaseconrmtheInvertersettingformaximumcharge/discharge
currentiswithintherangeof batteryrated charge/dischargecurrent.
The charge current can be set for 0-25A.
The remaining minimum capacity of the battery.
The discharge current can be set for 0-25A.
*Battery Awaken
-When the battery is low, you need to manually set the Battery Awaken
function -- start the Battery Awaken:
·Inverter will charge the battery when the PV input power> 1KW or inverter is
connected to the grid.
·Inverter will exit the Battery Awaken when battery voltage > discharge cut-
off voltage + 10V or Battery Awaken last > 2 hours.
-When inverter is in normal operation, and the battery power is sufficient,
start the Battery Awaken function, the inverter will exit the Battery Awaken
automatically.
Comment
Charge Absorp
Voltage
Charge Float
Voltage
Discharge Cut
Voltage
Charge Max
Current
Discharge Max
Current
Battery Awaken
When charging begins, it will enter constant votlage charging
mode in order to accelerate charging speed.
Please calculate this value based on lead-acid characteristic
parameter.
It will switch to oat charging mode after exiting constant
voltage charging mode.
Please calculate this value based on lead-acid characteristic
arameter.
When the battery voltage reachs this value in on-grid mode(no
PV power), battery will stop discharging and the system will go
into ILDE mode.When the battery voltage reachs this value in
off-grid mode, battery will stop discharging and the inverter will
stop exporting power from eps port with showing “BAT power
low” on LCD display.
Please calculate this value based on lead-acid characteristic
parameter and inverter maximum charge current limination.
Please calculate this value based on lead-acid characteristic
parameter and inverter maximum discharge current limination.
When the battery voltage drops too low to work, choose this
option “Yes to make battery charging from PV or grid forcbily.
>Function Control
Enable
Grid-tied Min set
>Min Capacity
10%
Grid-tied Min set
>Grid-tied Min Limit
Charger