43
Advanced Setup Table
cont. next page
Df = Factory Default Setting
Step# Description Pg# Range Df
1 Prog Mode 25 Non, 1 Day, 5/2 Day, 7 Day 7
2 Available Modes 25 Heat/Cool/Auto/Off, Heat/Cool Heat/Cool/
/Off, Heat/Off, Cool/Off Auto/Off
3 Backlight 17 On, Off Off
4 Backlight Level 17 Off thru 7 levels of brightness Level 5
5 Night Dimmer 17 On/Off Off
6 Night Dimmer Brightness 17 Off thru 7 levels of brightness 2 (20%)
7 Night Dimmer Start Time 17 12A-12A 8:00P
8 Night Dimmer Stop Time 17 12A-12A 6:00A
9 Current Service Filter Runtime Hours 21 0-1999 Hours 0
10 Current Service Filter Calendar Days 21 0-720 Days 0
11 Current Heat Runtime Hours 22 0-1999 Hours 0
12 Current Aux Heat Runtime Hours 22 0-1999 Hours 0
13 Current Cool Runtime Hours 22 0-1999 Hours 0
14 Current UV Lamp Calendar Days 22 0-720 Days 0
15 Current Humidifier Calendar Days 22 0-720 Days 0
16 Set Service Filter Runtime Hours 21 0-1950 hours 0
17 Set Service Filter Calendar Days 21 0-720 Days 0
18 Set UV Lamp Calendar Days 22 0-720 Days 0
19 Set Humidifier Calendar Days 22 0-720 Days 0
20 Language 17 English, Espanol, Francais English
21 Scrolling Method 18 “L-R Slow, L-R Fast, Word L-R “Whole
Slow, Word L-R Fast, Whole Words
Word L Slow, Whole Word R Center
Slow, Whole Word Ctr. Fast, Fast”
Whole Word Ctr. Slow”
22 Setpoint Limits 26 No, Use No
23 Max Heat Setpoint 26 35 - 99 Degrees 74
24 Min Cool Setpoint 26 35 - 99 Degrees 70
25 Cycles Per Hour 26 No Limit, 2, 3, 4, 5, 6 6
26 Compressor Minimum Off Minutes 26 0, 3, 5 Minutes 5
27 Min. Heat/Cool Setpoint Difference 26 0 - 6 Degrees 2
28 Number of Heat Stages 26 0 - 3 2
29 Number of Cool Stages 26 0 - 2 1
30 Number Of Compressor Stages 26 1, 2 1
31 Number of Aux Stages 26 0, 1, 2 0
32 1st Stage Deadband 27 1 - 6 Degrees 2
33 2nd Stage Deadband 27 0 - 10 Degrees 2
34 3rd Stage Deadband 27 0 - 10 Degrees 2
35 4th Stage Deadband 27 0 - 10 Degrees 2