Advanced Setup Table
Df = Factory Default Setting
Step# Description Pg# Range Df
67 Aux Output 32 Time, Temp, External, Free Time
Cooling, Venting
68 Aux Output Program Days 32 1 Day, 5/2 Day, 7 Day 1
69 Day Of Week To Program 32 Sunday - Monday (S - M) MTWTFSS
70 Aux Output Start Time 32 12am - 12am 7am
71 Aux Output Stop Time 32 12am - 12am 9pm
72 Copy 32 Yes, No No
73 Aux Output Temp Source 33 Thermostat, Outdoor, Remote, Remote
External
74 Aux Output Trigger Point Temp 33 0 - 120 Degrees 65
75 Free Cooling with A/C 34 With A/C, Without A/C With A/C
76 Free Cooling Usuable Temp 34 40 - 80 Degrees 65
77 Comfort Recovery 28 On, Off Off
78 Dry Contact Polarity 34 Open, Closed Open
79 Dry Contact Use 34 Condensate, Vacation, FDD Vacation
80 Humidity Polarity 29 Open, Closed Open
81 Dehumidify Polarity 29 Open, Closed Open
82 Dehumidify only with Cooling 29 On, Off On
83 Skyport 33 On, Off On
84 Local API 33 On, Off Off
85 ADR 38 On, Off On
86 ADR Action 38 Observe Setpoint Offset, Observe
Observe Static Setpoints SP Offsets
87 Event Max Cool Setpoint 38 65 - 90 90
88 Event Min Heat Setpoint 38 50 - 85 50
89 Static Cool Setpoint 38 65 - 85 82
90 Static Heat Setpoint 38 65 - 85 60
91 Cool Setpoint Offset 39 1 to 10 4
92 Heat Setpoint Offset 39 -1 to -10 -4
93 Press Fan To Clear All Messages 33