EasyManua.ls Logo

Spectra T950 - Page 29

Spectra T950
40 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 2—Site Requirements Physical Requirements
February 2019 Site Preparation GuideSpectra T950B Library
29
All values are measured at the AC input and include power supply
efficiency. The values are averages of observed hardware. In general, the
lighter the load on the power supplies, the less efficient they are. The
power supply efficiency in turn affects the power draw of all components.
Component Power Consumption
(watts)
Heat Load, Continuous
(BTU/hour)
Main frame
a
a. Assumes one 5/12 volt power supply and one 24 volt power supply; no drives or RIMs installed.
183 625
Drive frame
a
139 475
Media frame in frame
location 2 though 6
110 376
Media frame in frame
location 7 or 8
14 48
Bulk TAP frame 125 427
5/12 VDC power supply 33 113
24 VDC power supply 29 99
RIM 12 41
LTO - 8 Fib re Chann el
Full-Height
Read/write: 40
Idle: 15
b
Read/write: 136
LTO - 8 Fibre Ch a nn el or
SAS Half-Height
Read/write: 43
Idle: 14
b
Read/write: 164
LTO - 7 Fib re Chann el
Full-Height
Read/write: 31
Idle: 20
b
Read/write: 106
LTO - 7 Fibre Ch a nn el or
SAS Half-Height
Read/write: 31
Idle: 20
b
Read/write: 106
LTO - 6 Fib re Chann el Read/write: 28
Idle: 8
b
b. No cartridge loaded.
Read/write: 95
LTO-5, Fibre Channel Read/write: 37
Idle: 19
b
Read/write: 126
LTO-4, Fibre Channel Read/write: 37
Idle: 17.5
b
Read/write: 123
LTO-3, Fibre Channel Read/write: 29
Idle: 15
b
Read/write: 99
TS1155 technology Read/write: 60
Idle: 19
b
Read/write: 205
TS1150 technology Read/write: 55
Idle: 38
b
Read/write: 188
TS1140 technology Read/write: 53
Idle: 30
b
Read/write: 181

Other manuals for Spectra T950