IM-P713-01 CTLS Issue 1
40
AEL7 Series Electric actuator
Fig. 20 Anti-Condensation Heater Installation (8-20 KN)
5.4.2 Installation of Anti-Condensation Heater (8 – 20 kN)
With the actuator spindle in the fully extended position, the power supply safely isolated and the actuator
cover removed:
-
Check the anti-condensation heater kit for compatibility, completeness and signs of damage. Reject any
damaged parts immediately
-
Refer to Fig. 20 "Heater Installation 8-20 kN" for product orientation
-
Fix the heater to the main terminal plate as indicated with the M3 screws provided
-
Connect the wires as indicated in Fig. 22 Anti-Condensation Heater Wiring Diagram
Anti-Condensation
Heater Terminal Board