IM-P714-05 CTLS Issue 1
3
AEL8 Series Safety Information
Warning
The AUTOTUNE function will cause the valve and actuator to move. Make certain
that all outcomes have been properly accounted for. The AUTOTUNE function can
be stopped by pressing and holding any button during the commissioning cycle.
Warning
Prior to commissioning actuators fitted with the Shutdown Module, it is important to
refer to Section 6.7: Commissioning of Shutdown Module
-
Reconnect power supply
-
Set S2.8 to "ON" and the PROG LED will flash
-
Press and hold PROG button for 3 seconds, AUTOTUNE will commence
Commissioning LED status
LED
Status
BLUE RED GREEN ORANGE
Flash Waiting for AUTOTUNE start
Flash (alternate) Flash AUTOTUNE in progress
Flash AUTOTUNE complete
Quick Flash AUTOTUNE error
-
Once AUTOTUNE is complete the illuminated hand wheel will also confirm actuator status (Green if
control signal is connected.)
-
Set S2.8 to "OFF"
Illuminated Hand Wheel – Actuator status
Colour of handwheel Status
GREEN Ready for operation
BLUE Manual operation (Handwheel engaged)
ORANGE Warning (e.g. actuator operating at 50% speed)
RED Fault
For manual commissioning and DIP switch configuration please refer to IM-P714-02