IM-P402-130 EMM Issue 9
41
ALF - Alarm Filter - Applies to Alarm 1 and Alarm 2
Ranges OFF or ON
Default OFF
ALL - Alarm Latch - Applies to Alarm 1 and Alarm 2
Ranges OFF or ON
Default OFF
rEt - Retransmit
Ranges 4 - 20 mA or 0 - 20 mA
Default 4 - 20 mA
dr - Drive
Ranges rel (relay) or ret (retransmit)
Default rel (relay)
ACt - Action
Ranges In (reducing) or Out (incrementing)
Default In (reducing) with rising level
SP - Set Point
Ranges 3 – 97 (Interactive with control band)
Default 50
Resolution 1
Units %
Cb – Control band
Ranges 5 - 100 (Interactive with SP.)
Default 20
Resolution 1
Units %
CtL – Control
Ranges On / Off or Pro (proportional)
Default Pro