IM-P402-130 EMM Issue 9
40
10.8 Programming parameters / default settings
The default settings in this table are used in the 'quick start' guide - See Section 6.3.1.
InS - Input Select
Ranges 1-6 or 4.20
Default 1-6
Units Vdc or mA
InF - Input Filter
Ranges 2, 8 or 16
Default 2
Units Seconds
InA - Input Alarm (Out-of-range)
Ranges OFF or ON
Default OFF
AS1 - Alarm 1 select
Ranges Hi or Lo
Default Hi
AP1 - Alarm 1 percentage (of gauge glass)
Ranges 5 – 100 (high alarm) or 0 – 95 (low alarm)
Default 85 (high alarm) or 20 (low alarm)
Resolution 1
Units %
AS2 - Alarm 2 select
Ranges Hi or Lo
Default Lo
AP2 - Alarm 2 percentage (of gauge glass)
Ranges 5 – 100 (high alarm) or 0 – 95 (low alarm)
Default 85 (high alarm) or 20 (low alarm)
Resolution 1
Units %