Installation
VENTILATION REQUIREMENTS
This appliance needs 2m
3
/h of air per kw input.
This appliance must not be installed in a bed sitting room of less than 20m
3
or in
a bathroom or shower room.
If there are other fuel burning appliances in the same room, BS5440; Part2; 1989
should be consulted to determine the air vent requirements.
For room volumes between 5m
3
and 10m
3
, an air vent of 50cm
2
is required.
If the room has a door that opens directly to outside, or the room exceeds 10m
3
,
no air vent is required.
For room volumes of up to 5m
3
, an air vent of 100cm
2
is required.
All rooms require an openable window or equivalent and some rooms will require a
permanent vent as well.
NOTE: The use of a gas cooker results in the product ion of heat and
moisture in the room in which it is installed.
Always ensure that the kitchen is well ventilated. Keep natural ventilation holes open or
install a mechanical ventilation device. In particular, when using the grill or more than one
burner, open a window if a mechanical ventilation device is not in operation.
(continued)