www.stiebel-eltron.com HM (S)| HM(S) Trend | 9
INSTALLATION
Power supply
9.8 Safety valve
D0000042471
1
3
2
1 Drain hose
2 Fixing
3 Drain
Size the discharge outlet so that water can drain off unim-
peded when the safety valve is fully opened.
Ensure that the drain hose of the safety valve is open to the
outside.
Install the drain hose of the safety valve with a constant fall
to the drain. When installing the drain, never kink the drain
hose.
Secure the drain hose by suitable means, to prevent any hose
movement in the event of water being discharged.
10. Power supply
WARNING Electrocution
Carry out all electrical connection and installation work
in accordance with national and regional regulations.
WARNING Electrocution
The connection to the power supply must be in the form
of a permanent connection. Ensure the appliance can
be separated from the power supply by an isolator that
disconnects all poles with at least 3mm contact separa-
tion. This requirement can be met with contactors, circuit
breakers, fuses/MCBs, etc.
WARNING Electrocution
Before working on the appliance, isolate it from the
power supply at the control panel.
Note
The specified voltage must match the mains voltage. Ob-
serve the type plate.
Note
Observe the operating and installation instructions of the
heat pump manager and the heat pump.
The connection must only be carried out by a qualified contractor
and in accordance with these instructions.
Use cables with the relevant cross-sections. Observe the ap-
plicable national and regional regulations.
MCB/fuse
rating
Assignment Cable cross-section
B 16 A
Electric emergency/
booster heater
(DHC)
Three-phase
2.5 mm² for routing through a wall.
1.5 mm² with only two live cores and
routing on a wall or in an electrical con-
duit on a wall.
B 16 A
Electric emergency/
booster heater
(DHC)
1 phase
2.5 mm² for routing through a wall.
1.5 mm² when routing multi-core cables
on a wall or in an electrical conduit on
a wall.
B 16 A Control 1.5 mm²
Electrical data is provided in chapter "Specification / Data table".
!
Material losses
Provide separate fuses/MCBs for the two power circuits,
i.e. for the compressor and the electricemergency/boost-
er heater circuits.
Route the electrical cables into the appliance from below, along
the channel provided.
Then route the electrical cables through the strain relief
fittings.
Check the function of the strain relief fittings.