INSTALLATION
Settings
52 | LWZ 130 | LWZ 130 Enthalpie www.stiebel-eltron.com
General
Time/date
Day
f Set the current day of the week (Monday to Sunday).
Hour:Minute
f Set the current time (00:00 to 23:59).
Language
f Set the required language.
Air flow rate
f Select the air flow rate for the fan settings under "Air flow
rate" with "Flow rate, stage 0" to "Flow rate, stage 3".
Enable fan
The fans are deactivated in the delivered condition.
f Set the "Enable fan" parameter to "On".
11.2 Recommissioning
f Check whether filters are fitted in the unit. Never operate the
unit without filters.
f Check whether the condensate drain hose is damaged or
kinked.
11.3 Appliance handover
f Explain the appliance function to users and familiarise them
with how it works.
Note
Hand over these operating and installation instructions
to users for safekeeping. All information in these instruc-
tions must be closely observed. The instructions provide
information on safety, operation, installation and main-
tenance of the appliance.
12. Settings
Note
Observe the operating instructions. It explains which pa-
rameters can also be set by the appliance user.
12.1 Menus
Note
Some parameters are protected by a code. The factory
programmed code for qualified contractors is "1000".
Note
The parameters shown in grey can only be adjusted by
the service department.
f Press the "MENU" button to access the menus from the home
screen.
Menu Description
Info
Information about the actual values of the appliance
Diagnostics
Fault messages, operating time, maintenance intervals
Programs
Fan program
Settings
Adjustable values and functions
12.1.1 "Info" menu
Info
Value
Bypass status Off | On
Extract air temp. °C
Extract air hum. %
Extract air dew pt °C
Outdoor air temp. °C
Outdoor air hum. %
Outdoor air dew pt °C
Supply air temp. °C
Exhaust air temp. °C
Supply air fan control %
Supply air fan speed rpm
Supply air flow rate m³/h
Exhaust air fan control %
Exhaust air fan speed rpm
Exhaust air flow rate m³/h
Heating coil control %
Extract air diff. press. Pa
12.1.2 "Diagnostics" menu
Diagnostics
Value
Notification list
Clear notification list Off | On
Filter runtime h
Filter reset Off | On
Filter change interval d
Device operating time d
Fan operating time d
Diagnostics
Clear notification list
To clear the notification list, set this parameter to "On". Press "OK"
to confirm. Afterwards, "Off" is displayed again and the fault mes-
sages are deleted.
12.1.3 "Programs" menu
Programs
Value
Fan program
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
Sunday
Monday - Friday
Saturday - Sunday
Monday - Sunday