 Alarms
Para-
meter
Description of function
Setting range
Values
default

Assignment of alarm sensors, detailed
description of sensors in parameters

through

0: none
1: Sensor F1
2: Sensor F2
3: Sensor F3
4: Sensor F4
5: weighted mean value from F1 and F2
1

Upper limit value
0.0: inactive
+0.1...+99.0°C
10.0

Lower limit value
-99.0...-0.1°C
0.0: inactive
-10.0

Switching mode of alarm relay
0: on if alarm present (normal)
1: off if alarm present (inverse)
1

Switching hysteresis for alarm
0.1...15.0°C
2.0

Alarm suppression time after temperature
alarm
0...240 min.
10

Alarm suppression time after defrosting
0...240 Min 15

Alarm suppression time after control ON or
change of setpoint and/or alarm limits
0...300 Min.
180

Alarm suppression time, door open
0: no alarm
1 ... 600 sec.
180

Behaviour if temperature alarm disappears
again
0: without buzzer, delete automatically
1: with buzzer, delete automatically
2: without buzzer, with acknowledgement
3: with buzzer, with acknowledgement
1

Function buzzer and/or display
in the case of alarm (temp. alarm see

)
0: no display, no buzzer
1: display flashing only
2: buzzer active only
3: display flashing, buzzer active
4: like 2., can be acknowledged
5: like 3., buzzer can be acknowledged
6: like 5., recurring after

5

Buzzer recurring after acknowledgement
1 ... 120 min.
30

Reset MIN / MAX memory
0: -
1: reset MAX memory
2: reset MIN memory
3: Reset MAX and MIN memory
0

Display of current MAX memory
Measured value, not adjustable

Display of current MIN memory
Measured value, not adjustable

Function of high-pressure switch
Releases until permanent alarm
0: no permanent alarm
1..10 : releases per 15 min.
0

Function of low-pressure switch
Releases until permanent alarm
0: no permanent alarm
1...300 sec.
0

Password of parameter level

-99 ... 999 0