5. Previous warnings
12
13
12
If inlet pressure is higher than 5.5 bars, a pressure regulator
must be installed.
Water to be treated must be properly filtered, therefore, it is
recommended to install a pre-filter to guarantee the removal
of suspended particles, which may be swept along by inlet
water. It is recommended to use FILTERMAX self-cleaning
filters. Please contact your distributor for further information.
Failure to install an appropriate filter would result in particles obs-
tructing the inner holes or injectors of the system, thus affecting its
proper operation. .
5.2 Installation of the system
If the water softener must treat all the water supply of your
home, connect it to the general supply pipe before connec-
ting the rest of pipes, except for pipes supplying the outside.
Taps located outside the house must supply hard water. Due
to the sodium increase in softened water, it is not recommen-
ded to use it for watering, since it can negatively affect the
growth of plants and vegetables.
Should it be necessary to condition the installation of the
home in order to install the system in the foreseen location,
it must be carried out in accordance with the national regula-
tions in force, concerning internal electric and hydraulic ins-
tallations.
The planned location for the installation must have enough
space for the system itself, its accessories, connections, and
to carry out a proper maintenance.
The system should not be installed next to a heat source or
where it receives a direct flow of hot air.
The drain connection, where water from regeneration will be
driven, must be underneath the installation if possible. Drain
connection must always have a free outlet. The diameter of
this connection must have a minimum size of 1”. The maxi-
mum distance between the water softener and the drain in-
take cannot be placed higher than 6 m.
Drain hose Drain hose Drain hose
Underground drain Supply pipe Sink outlet
4 cm for
aeration
4 cm for
aeration
The surroundings and the environment where the system
and faucet are to be installed must meet the appropriate hy-
gienic and sanitary conditions.
Avoid external drips from pipes, drains, etc. onto the system.
Under no circumstances must the system be installed on
the outside.
Should softened water be supplied to a hot water or vapour
generator, it will be necessary to install a dependable check
valve between the water softener and the generator, in order to
prevent hot water from returning to the system and damaging
it.
It is recommended to install some valves for sample taking
both for treated and untreated water, as close as possible to
the water softener.
If there are quick-closing valves, it is recommended to install
a device to prevent water hammers.
The water softener only works with a power supply of 12
volts – 50 herz, which comes from the transformer included
in the system. Please make sure that the transformer is used
and that it is connected to a power supply of 220 – 240 V,
50Hz. Also, it must be ensured that the electrical installation of
the house is properly protected by a circuit breaker or a fuse.
If daytime pressure is higher than 5.5 bars, night-time pres-
sure may exceed the maximum. Please use the pressure-
reducing valve if necessary. (a pressure-reducing valve may
reduce the flow).
It is recommended to install a silicopolyphosphates filter in
the system’s outlet to protect the pipes from the corrosion of
softened water.