5.2. Choosing the shunt
If your are using a shunt supplied with the BSP-500, the BSP is configured for it and you can go directly to
the next section.
Otherwise, the measuring shunt must be configured. The shunts are meant to supply a measuring nominal
voltage at a nominal current. If you use the shunt supplied with the BSP-1200, the nominal current is 1200
A at 50 mV. If you use your own shunt, the current and the nominal voltage are given by the manufacturer
and are often printed on the shunt.
The parameters "Nominal Current of the shunt" {6017} and "Nominal Voltage of the shunt" {6018} of the
advanced menu enable to configure the BSP for a given shunt.
5.3. Reset the battery history to zero
If you install the BSP for the fisrt time or if the battery has been changed, you must reset the battery history
to zero, by means of the parameter {6003}.