8. Factory setting values
12 V 24 V 48 V
Level User
ref.
Parameter Unit Factory Min Max Factory Min Max Factory Min Max
Basic 6000 BASIC SETTINGS
Basic 6001 Nominal capacity Ah 110 20 20000 110 20 20000 110 20 20000
Basic 6002 Nominal discharge duration (C-rating) h 20 1 100 20 1 100 20 1 100
Basic 6017 Nominal shunt current A 500 10 10000 500 10 10000 500 10 10000
Basic 6018 Nominal shunt voltage mV 50 10 200 50 10 200 50 10 200
Expert 6003 Reset of battery history S S S S S S S S S
Basic 6004 Restore default settings S S S S S S S S S
Inst. 6005 Restore factory settings S S S S S S S S S
Expert 6016 ADVANCED SETTINGS
Expert 6031 Reset of user counters S S S S S S S S S
Expert 6019 Self-discharge rate %/
month
3 0 25 3 0 25 3 0 25
Expert 6020 Nominal temperature °C 20 0 40 20 0 40 20 0 40
Expert 6021 Temperature coefficient %cap/
°C
.5 0 3 .5 0 3 .5 0 3
Expert 6022 Charge efficiency factor % 80 50 100 80 50 100 80 50 100
Expert 6023 Peukert's exponent 1.2 1 1.5 1.2 1 1.5 1.2 1 1.5
Expert 6042 Activate the end of charge synchronization No/Yes No No Yes No No Yes No No Yes
Expert 6024 End of charge voltage level V 13.2 8 17.5 26.4 16 35 52.8 31.9 70.1
Expert 6025 End of charge current level %cap 2 0 20 2 0 20 2 0 20
Expert 6026 Minimum duration before end of charge s 240 5 300 240 5 300 240 5 300
Table 8.1. Factory setting values