26
AIR BOOSTER 2
EN/10.2018/IT30I © STULZ SpA – all rights reserved
6. Technical data
6.1. Application limits
Operation limits
Operating Temperature Min -10 °C
Max + 40 °C
Air humidity range 090%
Nominal power supply 230 V / 1ph / 5060 Hz
Voltage tolerance ± 10%
Frequency tolerance ± 2%
Storage limits
Temperature Min - 20 °C
Max + 50 °C
Humidity Max 90%
INFORMATION
Other limits not specified in this table can be found in the rest of this manual
6.2. Technical data
NOTES ON TECHNICAL DATA:
* Operating at nominal fan speed
** Measured at 2m distance from unit, in a free field, unit operating at nominal conditions.
According to ISO 9614.
This information must be made known to all personnel operating this unit and in the proximity
thereof.
Model Air Booster2
Nominal Airflow m
3
/h 2880
Maximum Airflow m
3
/h 5200
Power consumption* kW 0,075
Operating current (OA)* A 2
Maximum operating current (FLA) A 2,2
Raised floor overpressure* Pa 25
External sound pressure level** dB(A) 64
Weight kg 25
Height x Width x Depth mm 598  598  260