Stulz CompTrol 1002 - Alarm and Failure Table

Stulz CompTrol 1002
39 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1
2
2
1
21
3
E/0310/50/24
Display
Failures
Alarms
Table of Alarms and Failures
Consequences
------------
------------
------------
------------
Reheat 1 and 2
are switched off.
Humidifier off.
------------
All compon. off,
Valve is closing,
Damper is closing.
The alarms "HEA",
"HIP" and "LOP"
are inhibited.
Compressor 1 off.
Compressor 2 off.
Compressor 1 off.
Compressor 2 off.
--------------
--------------
--------------
Reheat, compressor
off, valve closed.
Humidifier off,
dehum. off.
All components off,
valve is closing.
Humidifier off.
All components off.
Exchange controller.
Meaning
Room temperature too high
Room temperature too low
Room humidity too high
Room humidity too low
Reheat 1 or 2 failure
Humidifier (20µS/cm) failure
Conductivity meter (5µS/cm)
Airflow 1 failure
Airflow 2 failure
Low pressure compressor 1
Low pressure compressor 2
Compressor 1 failure
Compressor 2 failure
Clogged filter
Auxiliary alarm 1
Auxiliary alarm 2
3°C > T > 50°C
Sensor break-down (temp.)
3% > r.h. > 97%
Sensor break-down (humidity)
Fire alarm / smoke detector
Water alarm
Controller defective
Alarm LED
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
Alarm Relay
X
X
X
X
X
X
-
X
X
X
X
X
X
-
X
X
X
X
X
X
Time Delay
about 30 s
about 30 s
about 30 s
about 30 s
about 3 s
about 5 min.
about 5 min.
about 20 s
about 20 s
3 min.
3 min.
3 s
3 s
about 5 min.
about 3 s
about 3 s
about 3 s
about 3 s
about 3 s
about 3 s
immediately
These failures can be alternatively chosen (DIP-switch 3).
After compressor start, otherwise 3 s.