EasyManua.ls Logo

Stulz CyberOne EC DX - 4.3.4 Component Replacement and Cleanup (Continued); Glossary

Stulz CyberOne EC DX
51 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
CyberOne EC DX IOM Manual
2. Turn off the water supply to the humidifier.
3. Turn the main power disconnect switch on the electric
box to the Off position and open the door of the unit
electric box.
4. Use vise grips to turn the shaft of the main power switch
to the On position to provide power for the humidifier
drain solenoid.
5. Follow the steps of the cylinder replacement procedure
in the humidifier installation and operation manual sent
under separate cover with your unit.
6. Close the door to the electric box and turn the main power
disconnect switch to the On position.
7. Turn the A/C unit On by pressing the Enter key.
8. Readjust the humidity to the desired set point.
If the humidifier is to be shut down for an extended period,
follow the steps of the Extended Shutdown procedure in
the humidifier installation and operation manual sent under
separate cover with your unit.
4.3.4.5 Air Filter Replacement
To change the airlters, open the front doors of the cabinet.
The air lters are accessed from inside the cabinet (except for
upflow units with rear return). For upflow units, thelters are
located behind the air intake grilles. For downflow units, the
lters are located at the top where the label “FILTER ACCESS”
appears. Remove the old lters from the trays. Insert the new
filter(s), ensuring the directional airflow arrows on thelters
are correct, then close the front doors.
40

Table of Contents