DE / 06-2016 / 1000687 © STULZ GmbH, Hamburg
-
84
-
Maintenance STULZ UltraSonic -System for duct humidication ENS 14 A - 18 A-
7
Reconnect the supply cable and assem-
ble the unit in reverse order.
CAUTION
Correct seating of seals
.
Make sure that seals are correctly seated!
IMPORTANT
Item Description
1 Oscillator
2 Atomizer PCB
3
Oscillator seal
CAUTION
Trapped cables
.
During installation, take care not to trap any
cables between parts of the housing!
IMPORTANT
6
Insert a new oscillator
including new seal, and screw tight.
CAUTION
Color coded cables
.
The cables are color coded and must not be inter-
changed!
ORG = orange cable, YEL = yellow cable
IMPORTANT
5
Detach the orange and yellow oscillator
cables from the atomizer PCB.
2
1
2
13
CAUTION
Correct position of oscillator
.
Make sure the oscillator is in the correct position!
(See illustrations in this section)
IMPORTANT