DE-18 USER MANUAL SECTION 5
58
put on the end of the sequencing list and the other
units shift towards the first (Lead Unit) position.
There are diagnostic displays in the Line 1 Selection
of the P-#'s (P-1). It is near the end of the list before
the 1/0 displays.
"Dl: 1234-5678-90T"
The numbers are that of the Units being called to run.
The "r” means that this Unit is being called to run.
The uncalled Units will have "O"s in their respective
place. Only in the Master will starting and stopping of
Units be apparent. The characters of the uncalled
units will be displayed with “+”s when the master is
planning on starting another Unit. And" “-”s when the
master is planning on stopping another Unit. If all
available Units are running ignore the "+"s and if only
one Unit is running ignore the "-"s.
This diagnostic display lets you know the percentage
of the Loaded RPM. RPM LD xx.x%"
REMOTE START / STAND-BY
CONTROLLER SET UP
INSTRUCTIONS
1. Press circle key
2. Press scroll up or scroll down key to find
code 64
3. Press circle key
4. Press scroll up or scroll down key to find
SETUP LOCKOUT (early models do not
have this feature – proceed to step 7 if the
machine does not have this feature)
5. Set the SETUP LOCKOUT to YES by press-
ing the scroll up or scroll down key
6. Press circle key
7. Press scroll up or scroll down to find MAS-
TER COM EN (Master Com Enable)
8. Set MASTER COM EN to NO by pressing
the scroll up or scroll down key
9. (NO is the default setting – this selection will
most likely already be chosen)
10. Press the circle key
11. Press scroll up or scroll down to find SLV
COM SEL
12. WARNING – IF SETUP LOCKOUT IS NOT
SET TO YES OR IF THE MACHINE DOES
NOT HAVE THE SETUP LOCKOUT FUNC-
TION THE MACHINE WILL START-UP
UPON COMPLETING STEP 13
13. Set SLV COM SEL to SLV1 by pressing the
scroll up or scroll down key
14. Press circle key – The machine may start-up
see step 12
15. Press scroll up or scroll down key to find P2
OVRD STRT
16. Press scroll up or scroll down key to select
the pressure at which the machine is desired
to start-up (75 psi minimum)
17. Press circle key
18. Press scroll up or scroll down key to find
SETUP LOCKOUT (early models do not
have this feature – proceed to step 20 if the
machine does not have this feature)
19. Set the SETUP LOCKOUT to NO by press-
ing the scroll up or scroll down key – The
machine will start if the discharge pressure
P2 is less than the P2 OVRD STRT pressure
20. Press scroll down key to get back to circle to
exit prompt
21. Press circle key
Notes:
1. If the discharge pressure P2 rises greater
than the discharge pressure setpoint + the R
LOAD PRS the machine will stop. R LOAD
PRS is an S parameter located in the code
64 settings which has a default setting of 5
psi.
S
ETUP OF AUTOSTART OPERATION
When the stop push button is pressed, the engine
will be brought to minimum RPM, the blowdown relay
will be de-energized. After the air intake delay (P-52
adjustment) has timed out, the intake solenoid valve
(4-way valve) will be de-energized to close. The cool-
down timer (P-12 adjustment) will start. The timing of
the cool-down will appear on the second line of the
display and count down ("COOLDOWN X SEC").
The controller will go to the COOLDOWN state for
the COOLDOWN duration.
After the COOLDOWN timer expires the CAT ECM
relay is de-energized to stop the engine. The drain
solenoid valves are energized for 60 seconds, the
drain on stop delay (S-6 adjustment), for a final drain.
The controller will return to the STANDBY state to