DE-18 USER MANUAL SECTION 5
64
P NUMBER SETTINGS (CODE 61)
Note: Where a setting has an x/y values, the value of
x refers to the 135 PSI mode and the value of y refers
to the 150 PSI mode, see the Pressure selected in P-
65 for its current value.
“P” Number Description Range Default Setting
P-0 Circle=Exit
P-1 Line 1 select
D1: XXXXXXXXXXX
RPM LD XXX.X %
P2 XXX PSI
SET PRS XXX PSI
*ENG XXX RPM
STS:
P1 XXX PSI
P4 XXX PSI
P3 XXX PSI
P4-P3 XXX PSI
T1 XXX F
T2 XXX F
T3 XXX F
T4 XXX F
T5 XXX F
T6 XXX F
*ENG OIL XXX PSI
*LOAD XX.X %
*CAT STS:
FUEL LVL XXX %
BATTERY XX.X VDC
CTL ERR X
(X=0 NO CTRL
X=POS LOADING
X=NEG UNLOADING)
(Over-ride NO CTRL
THRTL CTRL
DISCH CTRL)
I1-4 XXXX
I5-12 XXXX XXXX
O1-7 XXXX XXX
P-2 Last failure
P-3 CRNK attempts
0-6 4
P-4 Crank DSC RPM
300-500 RPM 500
P-5 CAT SD<RPM
500-1400 RPM 1100
P-6 B lockout DLY
0-120 Sec 15
P-7 Sender DLY
0-999 Sec 30
P-8 Crank DLY
0-30 Sec 15
P-9 Rest DLY
15-120 Sec 30
P-10 Warmup DLY
0-600 Sec 300