SECTION 5 DE-18 USER MANUAL
71
A
A
SD
AL
HI T3 SD
HI T4 AL
(S547-Port 3 - C277-AN3-RS485)
High temperature shutdown (See P-35) If P-35 is set to zero,
alarm only.
(S547-Port 3 - C277-AN4-RS485)
High temperature alarm (See P-36)
A
A
AL
SD
HI T5 AL
HI T5 SD
(S547-Port 3 - C277-AN5-RS485)
High temperature alarm (See P-38)
(S547-Port 3 - C277-AN5-RS485)
High temperature shutdown (See P-39) If P-39 is
set to zero, alarm only.
S SD LO P2 SD
TB1-24, 25 & 26 (S547-Port 1-AN4)
Low pressure shutdown (See P-40) If P2 limited is exceeded
AND P1 limit is exceeded or lost then SD, otherwise alarm only.
A AL LO FUEL LVL AL
TB1-27, 28 & 29 (S547-Port 1-AN5)
Low fuel level alarm (See P-43)
A SD LO FUEL LVL SD
TB1-27, 28 & 29 (S547-Port 1-AN5)
Low fuel level alarm (See P-44)
S AL LOST FUEL SENDER
TB1-27, 28 & 29 (S547-Port 1-AN5)
Lost analog signal for transducer2
B AL AIR FLTR DP AL
TB2-27 & 28 (S547-Port 3 - C267-DI2)
High differential pressure alarm (See 8.2)
B SD AIR FLTR DP SD
TB1-18 & 19 (S547-Port 1-AN2)(Switch)
High differential pressure shutdown (See 8.1)
BALCAT ECM WARN
TB2-25 (S547-Port 3 - C267-DI1)
Discrete Cat Panel signal (See 8.2)
B1 AL CAT ECM DIAGNSTC
TB2-29 (S547-Port 3 - C267-DI3)
Discrete Cat Panel signal (See 8.2)
B1 AL CAT ECM SERV REQ
TB2-29 (S547-Port 3 - C267-DI5)
Discrete
A SD CAT ECM SERV REQ
TB2-29 (S547-Port 3 - C267-DI4)
Discrete Cat Panel signal (See 8.2)
S1 AL CAT SD
TB1-41 & 42 / MDDM / Data Point 7 / (ECM)
MDDM has received data from the ECM that the Cat
Panel is shutdown
SSD CAT SD
TB1-41 & 42 / MDDM / Data Point 7 / (ECM)
MDDM cannot communicate with ECM
S SD LST 267 COM
Internal / Port 3 / C267
S547 cannot communicate with C267 (See P-62)
S SD LST 277 COM
Internal / Port 3 / C277
S547 cannot communicate with C277 (See P-63)
S
S
SD
SD
MDDM COM FAIL
LST ANLG P1 SD
Internal / Port 1 / MDDM
S547 cannot communicate with MDDM (See P-61)
TB1-30, 31 & 32 (S547-Port 1-AN6)
Lost analog signal for transducer2
Class SD/AL Description Source