E900H User Manual 2: Description
02250203-986 R03
Subject to EAR, ECCN EAR99 and related export control restrictions. 21
2.6 Compressor cooling and lubrication 
system, functional description
Refer to Figure 2-4. The compressor cooling and lubrica-
tion system is designed to provide adequate lubrication 
a
s well as maintain the proper operating temperature of 
the compressor. In addition to the cooler and fan, the sys-
tem consists of a main filte
r and thermal valve.
Fluid is used in the system as a coolant and a lubricant. 
Th
e fluid is housed in the receiver tank.
Upon start up, the fluid temperature is cool, and routing 
to 
the cooler is not required. The fluid first enters the ther-
mal valve and then flows on to the compressor unit, 
by
passing the cooler. As the compressor continues to 
operate, the temperature of the fluid rises and the ther-
mal valve element begins to shift. This forces a portion of 
the
 fluid to the fluid cooler. The cooler is a radiator-type 
that works in conjunction with a separate motor-driven 
fan. The fan blows air through the cooler removing the 
heat of compression from the fluid. From the cooler, the 
fluid is routed back to the thermal valve.
Before the temperature of the fluid reaches the valve set 
po
int, cooled fluid is mixed with warmer fluid. When the 
temperature of the fluid reaches 190°F (88°C), the ther-
mal element shifts completely cau
sing all fluid to flow to 
the cooler. After the fluid passes through the thermal 
valve it is then directed through the main fluid filter. 
There, the fluid is filtered in preparation for injection into 
the compression chamber and bearings of the compres-
sor unit. The filter has replaceable elements. After the 
fluid
 is properly filtered, it then flows on to the compres-
sor unit where it lubricates, seals and cools the compres-
sion chamber as well as lub
ricates the bearings and 
gears. 
2.7 Control system, functional 
description
The purpose of the compressor control system is to regu-
late the amount of air being compressed to match the 
a
mount of compressed air being used.
The capacity control system consists of a pneumatic inlet 
va
lve. The functional description of the control system is 
described below in four distinct phases of compressor 
operation. For explanatory purposes, this description 
applies to any compressor with an operating range of 150 
to 165 psig (10.3 to 11.4 bar). A compressor with any 
othe
r pressure range would operate in the same manner 
except for the stated pressures.
Start mode—0 to 50 psig (0 to 3.4 bar)
When the compressor <START> button is depressed, the 
sump pressure will quickly rise from 0 to 50 psig (0 to 
3.4 bar). During this period, both of the pressure regula-
tors and the solenoid valve are closed and the pneumatic 
inle
t valve is inoperative. The internal spring holds the 
inlet valve fully closed to reduce motor torque for starting. 
After six (6) seconds the solenoid valve will open, open-
ing the inlet valve, and the c
ompressor will run at full 
rated capacity. The rising compressor air pressure is iso-
lated from the service line in this phase by the minimum 
pr
essure valve set at approximately 50 psig (3.4 bar).
Full load mode—50 to 150 psig (3.4 to 10.3 bar)
When the compressed air pressure in the sump rises 
above 50 psig (3.4 bar), the minimum pressure valve 
op
ens, allowing compressed air to flow into the service 
line. A load signal is provided through a pressure reduc-
ing regulator set at 70 psig (4.8 bar) to maintain the inlet 
Figure 2-4: Cooling and lubrication system
1. Hose from oil cooler 5. Hose to oil cooler
2. Fan enclosure 6. Hose to unit
3. Fan guard 7. Fluid filter
4. Fan motor 8. Hose from separator 
tank