Quarter -Turn Electric Valve Actuator【OM Series】 Sun Yeh Ele. Ind. Co., Ltd. | 2021.11
6.7.4 Travel Setting
Press “MODE” 5 times to get into .
Press and hold “SET” around 5 sec until “LOC” comes on to enter Auto setting
mode.
When the Auto setting is completed, “LOC” comes off and the actuator stops
running. The travel setting is completed.
6.7.5 Signal Setting
If the travel end positions have not been set up properly per 0, please
follow steps below to recalibrate.
Input signal setting for fully-closed position
a. Press “MODE” several times until displays, then press “SET”
once to enter signal setting mode.
b. Press “UP” or “Down” until displays.
c. Press and hold “SET” around 3 sec until flashes.
d. Input signal according to the dip switch setting (1 V or 2 V or 4 mA).
e. Press “SET” once and then “MODE” 2 times to complete the input signal
setting for fully-closed position.
Input signal setting for fully-open position
a. Press ”MODE” several times until displays, then press “SET” once
to enter signal setting mode.
b. Press ”UP” or ”DOWN” until displays.
c. Press and hold ”SET” around 3 sec until flashes.
d. Input signal according to the dip switch setting (5 V or 10 V or 20 mA).
e. Press ”SET” once and “MODE” 2 times to complete the input signal setting
for fully-open position.