Quarter -Turn Electric Valve Actuator【OM Series】 Sun Yeh Ele. Ind. Co., Ltd. | 2021.11
Output signal setting for fully-closed position
Use a multimeter to measure the output signal in accordance with the
selected signal type.
a. Press “MODE” several times until displays, then press “SET” once
to enter signal setting mode.
b. Press ”UP” or ”DOWN” until displays.
c. Press and hold “SET” around 3 sec.
d. Select signal value by pressing “UP” or “DOWN” until the required value
is achieved.
e. Press “SET” once and “MODE” 2 times to complete the output signal
setting for fully-closed position.
Output signal setting for fully-open position
Use a multimeter to measure the output signal in accordance with the
selected signal type.
a. Press “MODE” several times until displays, then press “SET” once
to enter signal setting mode.
b. Press ”UP” or ”DOWN” until displays.
c. Press and hold “SET” around 3 sec.
d. Select signal value by pressing “UP” or “DOWN” until the required value is
achieved.
e. Press “SET” once and “Mode” 2 times to complete the output signal setting
for fully-open position.