EasyManuals Logo

Sungrow MVS4480-US User Manual

Sungrow MVS4480-US
56 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #25 background imageLoading...
Page #25 background image
19
Torque guidelines for accessories
Component Nominal Torque(In-
Ibs)*
Torque Range(In-
Ibs)
Bay-O-Net fuse cartridge end plug
70 60-80
Bay-O-Net fuse holder-to-cartridge
connection
70 60-80
Dry-well fuse canister clamp
60 40-80
Fluid-level sight plug
600 480-720
Fill plug
960 900-1020
Drain plug
960 900-1020
Drain valve 600 480-720
Automatic pressure relief device, panel-
mounted, 1/4” NPT
180 160-200
Automatic pressure relief valve, 1/2” NPT
180 170-190
Automatic pressure relief device, cover-
mounted
300 250-350
Neutral strap fastener (at ground pad)
160 140-180
Series/multiple, delta/wye or tap switch
mounting nut
120 96-144
MOV arrester disconnector mounting nut
(ECI brand)
120 96-144
Ground connector 160 140-180
Rotary load-break switch (Central Moloney
brand)
1200 1100-1300
Rotary load-break switch (Cooper Power
brand)
600 480-720
Rotary load-break switch handle (Allen
screw)
55 45-65
High voltage cable clamp
160 140-180
* When checking tightness of gasketed components, the measured torque will normally be
less than the nominal torque listed in the table above due to relaxation of the gasket material.
Additional tightening of bushing mounting hardware may cause the component to crack or
the gasket to become over-compressed.
User Manual 7 Service Preparation

Other manuals for Sungrow MVS4480-US

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Sungrow MVS4480-US and is the answer not in the manual?

Sungrow MVS4480-US Specifications

General IconGeneral
BrandSungrow
ModelMVS4480-US
CategoryInverter
LanguageEnglish

Related product manuals