Quick User Manual 6 Troubleshooting
21
Code
Description
Troubleshooting
003
Transient over-voltage.
The grid transient
voltage exceeds the
protective value.
1. This is a short-term fault due to grid
condition. Wait a moment for inverter
recovery.
2. If the fault persists, please contact
Sungrow Service Dept.
004
Grid under-voltage.
The grid voltage is
below the protective
value.
1. Check the grid voltage.
2. If the grid voltage exceeds the
permissible range of inverter protection
parameters, ask utility grid company for
solution.
3. If the grid voltage is within the permissible
range, contact Sungrow Service Dept.
005
Grid under-voltage.
The grid voltage is
below the protective
value, which is lower
than the protective
value of error 004.
1. This is a short-term fault due to grid
condition. Wait a moment for inverter
recovery.
2. If the fault persists, please contact
Sungrow Service Dept.
006
AC over-current.
The AC output current
exceeds inverter
allowable upper limit.
1. The inverter will resume if the output
current falls below the protection value.
2. If the fault persists, please contact
Sungrow Service Dept.
007
Transient AC
overcurrent.
1. The inverter will self-recover after several
seconds.
2. If the fault persists, please contact
Sungrow Service Dept.
008
Grid over-frequency.
The grid frequency
exceeds the protective
value.
1. Check the grid frequency.
2. If the grid frequency exceeds the
permissible range of inverter protection
parameters, ask utility grid company for
solution.
3. If the grid frequency is within the
permissible range, contact Sungrow Service
Dept.
009
Grid under-frequency.
The grid frequency is
below the protective
value.
010
Islanding
1. Check whether AC circuit breaker is
triggered.
2. Check whether AC cables are all firmly
connected.
3. Check whether grid is not in service.
4. If all conditions are OK and this fault still
occurs in the LCD screen, contact Sungrow
Service Dept.
011
DC injection
over-current.
The DC current
injection of AC current
exceeds the upper
limit.
1. Wait a moment for inverter recovery.
2. If the fault occurs repeatedly, contact
Sungrow Service Dept.

Table of Contents

Other manuals for Sungrow SG2K5-S

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Sungrow SG2K5-S and is the answer not in the manual?

Sungrow SG2K5-S Specifications

General IconGeneral
BrandSungrow
ModelSG2K5-S
CategoryInverter
LanguageEnglish

Related product manuals